CATALOG NO.: 5000.59B
Effective Date: 4-09-08
Replaces:
3-15-99
Installation and Operating Manual
T-3
Raypak B6000 Modbus
System Protocol Interface
T-3 Communications Interface
Raypak B6000 Boiler Controller
to Modbus Interface Card
P/N 240729 Rev. 3
T-3 (Raypak B6000 System Protocol Interface)
Quantity
Contents
COMPACT DISC (CD)
1
1
1
T-3
EPROM (CPX.XNMn) in small black ESD box
Check packaging for damage or missing components.
IMPORTANT NOTICE: These instructions are intended for the use by qualified personnel only,
specifically trained and experienced in the installation of this type of equipment and related sys-
tem components. Installation and service personnel may be required by some states to be
licensed. If your state is such, be sure your contractor bears the appropriate license. Only quali-
fied persons shall attempt to repair this equipment. Repair must be according to these instruc-
tions.
WARNING: Improper installation, adjustment, alteration, service or maintenance may damage
the equipment, create a hazard resulting in asphyxiation, explosion, fire, electric shock, personal
injury or property damage and will void the warranty.
CAUTION: ONE SUPPLY SOURCE. TO REDUCE THE RISK OF ELECTRIC SHOCK,
DISCONNECT ALL CONNECTIONS BEFORE SERVICING.
CAUTION: RISK OF ELECTRIC SHOCK, DISCONNECT SWITCH IS REQUIRED TO DE-
ENERGIZE THE EQUIPMENT BEFORE SERVICING.
NOTE: Minimum 18 AWG, 105°C, stranded wire must be used for all low voltage (less than 30
volts) external connections to the unit. Solid conductors should not be used because they can
cause excessive tension on contact points. Install conduit as appropriate. All high voltage
wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.
Thank you for selecting the Raypak B6000 Boiler Management System and the Raypak
Communication Interface. It is our sincere hope that you will enjoy its power, ease of use and
energy saving features.
Please follow the instructions carefully to insure proper installation.
FORWARD
The Raypak Communication Interface is designed to allow the Communication Interface System
to monitor and control the Raypak B6000 Boiler Management System.
3
T-3 INSTALLATION AND MOUNTING
The T-3 Module should be mounted on a permanent base not subject to vibrations, moisture or
dust. It should be readily accessible, for serviceability.
DIMENSIONS AND WEIGHT
15 3/4” H
14 LBS
8”
W
5 3/4” D
MECHANICAL INSTALLATION
Mount the System Protocol Interface within five (5) feet of B6000 System Control Box.
The Gateway enclosure must be mounted vertically with conduit holes facing downward. Conduit
holes are provided to accommodate standard conduit fittings. Additional or larger conduit fit-
tings that may be required should be located on the bottom of the module. Mount the Interface
with 3/8” or 1/4” hardware in four (4) places.
A Minimum of six (6) inches clearance on all sides is required and a minimum of eighteen (18)
inches clearance from the front is required for service access. The hinged side of the box is to
the right and the clearance (minimum 3” from bolt hole on the right side) should be sufficient to
open the cover.
A sub-panel containing the disconnect switches and surge suppressors is required at or near the
equipment location(s).
For accessibility remove the lower interior panel, by removing the four (4) access screws.
INSTALL CONDUIT AS APPROPRIATE.
ELECTRICAL CHARACTERISTICS
120 VAC, 0.25A, 60 Hz
ELECTRICAL INSTALLATION
120 VAC FEEDER CIRCUITS
Install a surge protection device sized appropriately for your installation.
Install separate disconnect means for each load. Pull in appropriately sized wire for equipment
as defined by NEC and/or local code.
It is strongly recommended that the Communications Interface, B6000 System Control Module
and the B6000 Boiler Control Module be supplied from the same source power.
4
WIRING T-3
1. Turn off power to the B6000 System Control Box.
2. Open front door of System Protocol Interface Gateway Enclosure.
3. Remove four screws and the lower cover, revealing the field wiring blocks.
4. Attach wires from interface card to the field wiring side of left terminal block (N+, N-,
GND, NC). Refer to diagram in this user manual.
5. Open front door of the B6000 System Control Box.
6. Remove four screws and the lower cover, revealing the field wiring blocks in lower left.
7. Run RS-485 cable (provided) to the lower left field wiring terminal in the
B6000 System Control box. Attach wires to the upper four terminals as follows:
BLU/WHT
WHT/BLU
ORG/WHT
SHIELD
to
to
to
to
+
-
(1)
(2)
COM (3)
GND (4)
8. The EPROM (CPX.XNMn), in small black ESD box, must be installed in
place of the current EPROM.
9. View the B6000 System Control Board picture on the next page. Note location of
EPROM, U4.
10. Remove four screws holding upper panel with display screen and keypad. Carefully
remove upper panel and turn over exposing B6000 System Control Board, (see next
page).
11. Using ESD procedures carefully remove the EPROM from location U4.
12. Again using ESD procedures carefully install the EPROM labeled CPXXNM or CPXXM
into location U4.
13. Re-assemble B6000 System Control Box.
14. Turn power on to B6000 System Control Box.
15. Connect 120 VAC (hot, Neutral, ground) to T-3 at right terminal block.
16. Re-assemble.
5
B6000 SYSTEM CONTROL BOARD
CHECK YOUR POWER SOURCE
AC = 108 Volts AC Minimum, 132 Volts MAX
AB = 108 Volts AC Minimum, 132 Volts MAX
BC = Must be less than 1.0 Volts AC
6
7
11.0.
T-3
Revision 1.0
Raypak B6000 Modbus™
Protocol Interface
Successful application of the T-3 card requires a reasonable work-
ing knowledge of the Raypak B6000 Boiler Control, and the applica-
tion in which the combination is to be used. For this reason, it is
important that those responsible for implementing the T-3 satisfy
themselves that the T-3 and B6000 Boiler Control combination will
meet the needs of the application.
Please Read this Notice
This manual is provided to assist the user. Every attempt has been
made to ensure that the information provided is accurate and a true
reflection of the product’s installation requirements. In order to en-
sure a complete understanding of the operation of the T-3 with B6000
Controller, the user should read all applicable Raypak documenta-
tion on the operation of the B6000.
WARNING
The T-3 card will allow remote access to commands in the
B6000 Controller. The User is responsible for ensuring that
any applicable regulations concerning the remote operation
of equipment are adhered to.
8
11.1. Product Specifications
The T-3 card is a hardware product designed to be the communications front end
for the Raypak B6000 Boiler Control and a modbus Master Host.
The product includes the following functionality:
Modbus Slave Specifications
•
Protocol Modes:
RTU mode with CRC-16 error checking
Supported Modbus Function codes:
•
2
3
4
6
8
Read Input Status
Read Multiple Data Registers
Read Input Registers
Preset (Write) Single Data Register
Loopback Test (Test 0 only)
•
•
Supports broadcast commands from host
RS-485 electrical interface
Raypak B6000 Interface
•
•
RS-485 electrical interface
Emulates Raypak Modem address and functionality
General Specifications
Configurations via dip switches
SlaveAddress, Baud and Parity
•
Hardware Specifications
•
•
•
•
4” X 5” form factor
Two male 9-pin D Shell connectors
Communications Status lights -Active and Fault for each port
9 to 30 VDC external power
9
11.2.0
Slave Port Functionality
Modbus Communications
11.2.1
The T-3 Modbus Slave card runs the RTU version of the Modbus protocol. This capability
allows the module to communicate data from a Raypak B6000 Boiler Control to a Modbus
Master host, and vice-versa. The module supports both point-to-point implementation as
well as multi-drop implementations.
The following discusses the functional capabilities of the T-3 card.
11.2.1.1
Command/Reply Cycle
Successful communications between the card and a host will always con-
sist of the following two transactions:
Command: Message from master giving instruction to slave.
Reply: Response to command.
A slave station will respond to a master issued command in several ways.
Data Message: If the command was executed by the T-3 board, the re-
sponse message will include the data requested, or an acknowledge-
ment that the command was executed.
Error Message: If the command could not be executed by the T-3
board, for whatever reason, an error response message is transmitted to
the master. The error response message consists of the original function
code (ORed with 80hex) and error code.
No Reply: If the master does not detect a reply within its time-out pe-
riod, the master should retransmit the command, before a time out error is
issued. If the Slave could not decode the message or an error occurred
preventing the Slave from recognizing the message, no response will be
issued.
11.2.1.2
Command Types
The T-3 can respond to three types of commands from the master;
read data, write data, and a diagnostic command. These are overviewed
below:
Read Data:
The following type of data read commands are supported:
Read Input Status
Read Multiple Registers
2
3
4
Read Input Registers
Write Data:
6
The Following data write command is supported:
Single Register Write
Diagnostics:
8
The diagnostic command is supported:
Loopback test - Code 0
11.2.1.3
Command Error Checking
When the T-3 cannot execute a command, an error code is generated and
returned to the master. Error codes generated at the slave will usually be
indicative of an illegal function, an illegal address, bad data, or the inability
to complete a transaction because of a network problem.
10
11.2.1.4
Data Integrity
As in all good protocols, there must exist a level of data integrity
checking to verify, with some degree of assurance, the quality of
the transmitted data. The Modbus protocol supports two types of
error checking:
•
•
RTU Mode: 16 bit cyclic redundancy check (CRC-16)
One bit parity check
CRC-16: When the master generates a message, a 16 bit CRC
value is added to the end of the transmitted packet. The CRC
value is generated using a series of the bit shifts and manipulations.
The receiving station executes the same calculation of the data
and verifies the transmitted CRC. Any discrepancy will cause the
message to be disregarded.
Parity: Parity checking can be added as an additional level of data security.
If parity checking is selected, even or odd parity can be implemented.
11.2.2
Modbus Register Map
Apredefined register map has been provided for the T-3 unit. This
map is detailed in Appendix A.
11
Hardware Setup
11.3.0
11.3.1.1
1500 Interface Card Setup
11.3.1.1 Connecting Power to the T-3 Card
The T-3 Card requires an external source of DC voltage. The
DC source voltage should be between 9V and 30V. The power is
connected to TB1, located near the two 9 pin serial port connec-
tions.
The connection to TB1 is as follows:
TB1-1
TB1-2
9-30 VDC (+)
Common (-)
11.3.1.2 Dip Switch Configuration
The T-3 card is configured primarily through two sets of dip
switches. These switches are read initially on power up only.
The function of the dip switches is as follows (a value of one (1)
is registered when the a switch is in the ON position):
SW 2
1 2
3
4
5
6
7
8
SW 1
OFF Position:
OFF Position:
1 2
3
4
5
6
7
8
O
F
F
O
F
F
•
• • • • • •
•
• • • • •
↓
•
•
•
↓
ON Position:
ON Position:
SW1 : Modbus Port Configuration
Switch
Position
Function
Baud Rate
Selection
Positions
1
1
2
3
3
0
0
0
0
1
1
1
1
2
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
300
600
1200
2400
4800
9600 -
19200
19200
Factory Settings
*
*
9600, No Parity, Address Bit 1
4
5
Parity
Selection
5
0
0
1
1
4
0
1
0
1
None -
Odd
Even
*
Invalid
6
7
8
Not Used
SW2 : Modbus Slave Address Configuration
Switch
Position
Function
Baud Rate
Address
Select
Positions
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Address Bit 0 Value = 1
Address Bit 1 Value = 2 -
Address Bit 2 Value = 4
Address Bit 3 Value = 8
Address Bit 4 Value = 16
Address Bit 5 Value = 32
Address Bit 6 Value = 64
Address Bit 7 Value = 128
*
12
Example Addresses = 0 to 33
Example Addresses = 34 to 63
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
4
0
0
0
0
0
0
0
0
1
1
1
0
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Address
Invalid
1 *
2
3
4
5
6
7
8
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
3
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
2
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
* Indicates Factory Setting
13
The parameters are defined as follows:
Modbus Slave Address: Each of the separate drop offs of a Modbus
host must have a different slave address. The slave address is
selected by encoding the slave address in a binary form using the
dip switches.
11.3.1.3 T-3 Jumper Configurations
The T-3 card has five sets of jumpers on the board. Generally, the
default jumper positions will be adequate for most applications, with
JP4 and JP5 being the only jumpers that should ever need to be
reviewed. For completeness, we provide the following discussion on
all the jumper locations:
Jumper
JP1
JP2
Description
Hardware Reset
Raypak Port
Power (P2)
Positioning
Not Used
1-2 Non-Isolated Power
2-3 Isolated Power
Default
1-2
JP3
JP4
Raypak Port
Ground (P2)
Modbus Port (P1)
Termination
Resistor
Modbus Port (P1)
RS-232 or
1-2 Non-Isolated Power
2-3 Isolated Power
1-2 Connect 120 ohms on
Rx lines (multidrop only)
2-3 Disconnect 120 ohms
1-2 RS-232 Select
1-2
2-3
JP5
2-3
2-3 RS-422/485 Select
RS-422/485 Select
11.3.2 B6000 Communications
The B6000 communications interface has been hard coded (i.e., no dip switches
are required to configure this port) to operate at the following default conditions:
Baud
Parity
Stop Bits
9600
None
2
The T-3 card emulates the modem card that is normally connected to the
B6000 Controller.
14
11.4.0
Modbus Protocol Support
11.4.1
Modbus Commands
The T-3 card supports a command subset of the Modbus Specification consisting
primarily of the Function Codes required to read and write data. The following sections
detail the different commands supported by the card.
Function
Code
2
Address
Command
Read Input Status
Slave Driver
Range
Comments
Module returns binary data from the
10001
to “Input Status” register space.
10331 & 10833
3
4
6
8
Read Multiple
Registers
40001
to
40138
The Module returns word data from
the register space. The module will
support up to 125 words of data in
one command.
Read Input Registers
30001
to
30138
The module returns data from the
“Input register” space in the module.
The module will support up to 125
words of data in one command.
Single Register Write 40001 to 40030 This is a register write command
and allowing a host to change values in
40133 to 40138 the B6000 unit by writing a register
value.
Loopback Test
Test 0
This is a diagnostic command which
echoes the command sent.
11.4.2
Modbus Error Codes
The T-3 card supports the following Modbus Error Codes:
Code
Name
Description
0
1
2
All OK
Illegal Functions
Bad Data Address
The module is operating as desired
An illegal function code request is being attempted
The address, or the range of addresses, covered by
a request from the master are not within allowed
limits.
3
4
Bad Data Value
The value in the data field of the command is not
allowed.
Incomplete Response
Detected
This error indicates that an incomplete response was
received to a master query. Often this will indicate
that the slave device may be responding too quickly
or that there may be excessive noise on the line.
The module busy status code is returned when a
write command from the master has not yet been
completed when a second write command is received
6
Module Busy
15
11.5.0
Diagnostics
Several hardware diagnostics capabilities have been implemented using the LED indicator lights on
the front of the T-3 card. The possible conditions as indicated by the lights are:
11.5.1 LED Indicators
Several hardware diagnostics capabilities have been implemented using the LED indicator
lights on the front of the module. The possible conditions as indicated by the lights are:
Name
Modbus (P1)
ACTIVE
LED
D1
Color
Green
Status
Blinking
Indication
The T-3 is receiving a command
from the Modbus Host
Steady
ON
or
OFF
The T-3 is not detecting a valid
command. If the master is
transmitting, be sure all dip
switches are set correctly and that
the cable connection is correct.
The T-3 is processing a B6000
command
Raypak (P2)
ACTIVE
D2
Green
Blinking
Steady
ON
or
OFF
ON
Check cable connection to verify
polarity of terminations between
T-3 card and B6000 (See Appen-
dix B)
The Modbus port has detected a
communications error condition.
See Section 4.2
Modbus (P1)
COMM
D3
D4
Red
Red
or
ERR
Blinking
OFF
ON
No error conditions at this time.
The T-3 card has detected a
communications error condition.
No error conditions at this time.
Raypak (P2)
FAULT
OFF
Should the configuration dip switches select an invalid address or an
invalid baud rate, the LED indicators will alternate in the on/off fashion
on 1/2 second intervals until correct values are selected.
16
11.6.0
ProSoft Support, Service and Warranty
11.6.1 Technical Support
ProSoft Technology survives on its ability to provide meaningful support to its customers.
Should any questions or problems arise, please feel free to contact us at:
ProSoft Technology, Inc.
9801 Camino Media
Suite 105
Bakersfield, CA 93311
(805) 664-7208
(805) 664-7233 FAX
Before calling for support, please prepare yourself for the call. In order to provide the best
and quickest support possible, we will most likely ask for the following information (you
may wish to fax it to us prior to calling):
1. Product Serial and Version Number
2. T-3 Configuration Information
-
-
-
Dip Switches
Jumpers
Communication cabling
11.6.2 Service and Repair
The T-3 card is an electronic product, designed and manufactured to function under
somewhat adverse conditions. As with any product, through age, misapplication, or any
one of many possible problems, the card may require repair.
The T-3 product has a one year parts and labor warranty according to the limits
specified in the warranty. Replacement and/or returns should be directed to the distribu-
tor or Original Equipment Manufacturer from whom the product was purchased. If you
need to return the card for repair, it is first necessary to obtain an RMAnumber from
ProSoft Technology. Please call the factory for this number and display the number
prominently on the outside of the shipping carton used to return the card.
17
LIMITED WARRANTY
T-3
SCOPE OF WARRANTY:
Raypak, Inc. (“Raypak”) warrants to the original owner the T-3 to be free from defects in materials and workmanship under normal
use and service for the applicable warranty period. In accordance with the terms of this Limited Warranty, RAYPAK will furnish a
replacement or repair, at our option, any defective part which fails in normal use and service during the applicable warranty period. The
replacement or repair will be warranted for only the unexpired portion of the original Warranty Period.
APPLICABLE WARRANTY PERIOD
The effective date of warranty coverage is the date of original installation, of the Control System, by a qualified electrician or by a
RAYPAK authorized service technician. The Applicable Warranty Period is one (1) year from the effective date.
WARRANTY EXCLUSIONS
This Limited Warranty does not apply:
1. if the control system is not properly installed by a qualified technician in accordance with manufacturer’s installation instructions,
applicable codes, ordinances and good trade practices,
2. to damage or malfunctions resulting from failure to properly install, operate or maintain the system in accordance with the
manufacturer’s instructions;
3. if the rating plate’(s) or serial number(s) are altered, defaced or removed;
4. if the System is modified in any way or used with any non-factory authorized accessories or components;
5. to damage or failure from abuse, accident, act of nature, fire, flood, freezing or the like;
6. to accessories, rubber or plastic parts, light bulbs or glass parts;
7. if the System is moved from its original installation site; or if the original owner no longer owns the site or the System.
LABORAND SHIPPING COSTS
This Limited Warranty does not cover labor costs for service, removal or reinstallation of any part nor shipping charges to or from
RAYPAK’S designated repair center or to or from the installation site. All such costs are your responsibility.
HOW TO MAKEAWARRANTY CLAIM
To make a warranty claim, promptly ship (postage prepaid) or carry the defective part to a designated RAYPAK Service Dealer or
Service Station in the United States, supplying proof of purchase and date of purchase and date of installation and the model and serial
numbers. If you cannot locate a dealer, contact RAYPAK’S Service Department at the address/telephone listed below. Raypak reserves
the right at all times to inspect the claimed defect and verify warranty coverage at its factory.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by RAYPAK. No one is authorized to make any other warranties on Raypak’s behalf. ANY IMPLIED
WARRANTIES, INCLUDING MERCHANTABILITYOR FITNESS FORAPARTICULAR PURPOSE, SHALLNOTEXTEND BEYONDTHEAPPLI-
CABLE WARRANTYPERIOD SPECIFIEDABOVE. RAYPAK’S SOLE LIABILITY WITH RESPECTTOANYDEFECTSHALLBEAS SETFORTH
IN THIS LIMITED WARRANTY.ANY CLAIMS FOR INCIDENTALOR CONSEQUENTIALDAMAGES (INCLUDING DAMAGE FROM WATER
LEAKAGE) ARE EXCLUDED. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGALRIGHTS,AND YOU MAYALSO HAVE OTHER RIGHTS WHICH VARY FROM
STATETO STATE.
We suggest you immediately complete the information below and retain this Limited Warranty Certificate in case warranty service is
needed.
RAYPAK, INC. SERVICE DEPARTMENT
2151 Eastman Avenue, Oxnard, CA 93030
(805) 278-5300 FAX (805) 278-5489
The following information must be provided when you write or call:
Original Owner
Complete Mailing Address
City
Daytime Telephone Number
State
Zip Code Installation Site
Model Number
Date of Installation
Contractor/Installater
Serial Number
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (805) 278-5489
Litho in U.S.A.
APPENDIX A
Modbus Register Map
A-1
19
Raypak Modbus Register Assignments
Function Function Function
Type
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
2
4
3,6
Description
Setpoint
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30015
30016
30017
30018
30019
30020
30021
30022
30023
30024
30025
30026
30027
30028
30029
30030
30031
30032
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027
40028
40029
40030
40031
40032
Day Setpoint (Desired water temp @70F)
Nitesetback Night Setback (Desired water temp @ 70F)
Ratio Out
Throttling
Modulating Step (%) min 5% steps
Wait State Time (Sec)
Outdoor Cut off Temperature (O/C)
Control Band (degrees F Tolerance from TAR) (C/B)
Lead Boiler Number (1 to Number of Boilers)
Number of Boilers
TP - Boiler Pump Delay (Min) Boiler #1
TP - Boiler Pump Delay (Min) Boiler #2
TP- Boiler Pump Delay (Min) Boiler #3
TP- Boiler Pump Delay (Min) Boiler #4
TP- Boiler Pump Delay (Min) Boiler #5
TP- Boiler Pump Delay (Min) Boiler #6
TP- Boiler Pump Delay (Min) Boiler #7
TP- Boiler Pump Delay (Min) Boiler #8
TS - Ignition Time (Sec) Boiler #1
TS - Ignition Time (Sec) Boiler #2
TS - Ignition Time (Sec) Boiler #3
TS - Ignition Time (Sec) Boiler #4
TS - Ignition Time (Sec) Boiler #5
TS - Ignition Time (Sec) Boiler #6
TS - Ignition Time (Sec) Boiler #7
TS - Ignition Time (Sec) Boiler #8
Time - Hrs
1-200 = 0.1 - 20.0 in 0.1 increments
Delta T of all boilers in system (Normally 20 / # boilers)
Time - Min
Time - DWK
Lead Change Hours
Bit 0 = Night Setback on
Bit 0 = Fault Status )1=system fault)
Bit 1 = Call Out Request (1 = Yes)
10001
10017
10018
Night Setback
Controller LED Status
Controller LED Status
R
R
R
R
R
R
R
R
R
R
R
R
R
30033
30034
30035
30036
30037
30038
30039
30040
30041
30042
30043
40033
40034
40035
40036
40037
40038
40039
40040
40041
40042
40043
Outdoor Temperature + 35
Water Temperature + 35
Target Temperature (TAR)
Valve Position (0-100%) - Boiler #1
Valve Position (0-100%) - Boiler #2
Valve Position (0-100%) - Boiler #3
Valve Position (0-100%) - Boiler #4
Valve Position (0-100%) - Boiler #5
Valve Position (0-100%) - Boiler #6
Valve Position (0-100%) - Boiler #7
Valve Position (0-100%) - Boiler #8
30044
40044
Boiler #1 Status Word
Boiler Not On Line
Boiler #1
(0 = Normal, 1 = Alarm)
bit
0
R
R
R
R
R
R
10209
10210
10211
10212
10213
10214
1
2
3
4
Boiler Operation
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
5
A-2
20
R
R
R
R
R
10215
10216
10217
10218
10219
6
7
8
9
High Limit
(0 = Normal, 1 = Alarm)
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
30045
30046
30047
30048
40045
40046
40047
40048
bit Boiler #2 Status Word
Boiler #2
R
R
R
R
R
R
R
R
R
R
R
10225
10226
10227
10228
10229
10230
10231
10232
10233
10234
10235
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
bit Boiler #3 Status Word
Boiler #3
R
R
R
R
R
R
R
R
R
R
R
10241
10242
10243
10244
10245
10246
10247
10248
10249
10250
10251
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
bit Boiler #4 Status Word
Boiler #4
R
R
R
R
R
R
R
R
R
R
R
10257
10258
10259
10260
10261
10262
10263
10264
10265
10266
10267
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
bit Boiler #3 Status Word
Boiler #5
R
R
R
R
R
R
R
R
R
R
R
10273
10274
10275
10276
10277
10278
10279
10280
10281
10282
10283
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
A-3
21
30049
30050
30035
40049
40050
40051
bit Boiler #6 Status Word
Boiler #6
R
R
R
R
R
R
R
R
R
R
R
10289
10290
10291
10292
10293
10294
10295
10296
10297
10298
10299
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
bit Boiler #7 Status Ward
Boiler #7
R
R
R
R
R
R
R
R
R
R
R
10305
10306
10307
10308
10309
10310
10311
10312
10313
10314
10315
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
bit Boiler #3 Status Ward
Boiler #8
R
R
R
R
R
R
R
R
R
R
R
10321
10322
10323
10324
10325
10326
10327
10328
10329
10330
10331
0
1
2
3
4
5
6
7
8
9
Boiler Not On Line
Boiler Operation
Low Water Cutoff
Low Pressure Water
Low Pressure Gas
High Pressure Gas
High Limit
Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
Manual Override
Flow Switch
(0 = Normal, 1 = Alarm)
(0 = Firing, 1 = Ready)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
(0 = Normal, 1 = Alarm)
10 No Pilot
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
30052
30053
30054
30055
30056
30057
30058
30059
30060
30061
30062
30063
30064
30065
30066
30067
30068
30069
40052
40053
40054
40055
40056
40057
40058
40059
40060
40061
40062
40063
40064
40065
40066
40067
40068
40069
Setpoint
Day Setpoint (Desired water temp @70F)
Nitesetback Night Setback (Desired water temp @ 70F)
Ratio Out
Throttling
Modulating Step (%) min 5% steps
Wait State Time (Sec)
Outdoor Cut off Temperature (O/C)
Control Band (degrees F Tolerance from TAR) (C/B)
Lead Boiler Number (1 to Number of Boilers)
Number of Boilers
TP - Boiler Pump Delays (Min) Boiler #1
TP - Boiler Pump Delays (Min) Boiler #2
TP - Boiler Pump Delays (Min) Boiler #3
TP - Boiler Pump Delays (Min) Boiler #4
TP - Boiler Pump Delays (Min) Boiler #5
TP - Boiler Pump Delays (Min) Boiler #6
TP - Boiler Pump Delays (Min) Boiler #7
TP - Boiler Pump Delays (Min) Boiler #8
1-200 = 0.1 - 20.0 in 0.1 increments
Delta T of all boilers in system (Normally 20 / # boilers)
A-4
22
R
R
R
R
R
R
R
R
R
R
R
R
R
30070
30071
30072
30073
30074
30075
30076
30077
30078
30079
30080
30081
30082
40070
40071
40072
40073
40074
40075
40076
40077
40078
40079
40080
40081
40082
TS - Boiler Start Times (Sec) Boiler #1
TS - Boiler Start Times (Sec) Boiler #2
TS - Boiler Start Times (Sec) Boiler #3
TS - Boiler Start Times (Sec) Boiler #4
TS - Boiler Start Times (Sec) Boiler #5
TS - Boiler Start Times (Sec) Boiler #6
TS - Boiler Start Times (Sec) Boiler #7
TS - Boiler Start Times (Sec) Boiler #8
Time - Hrs
Time - Min
Time - DWK
Lead Change
Hrs Remaining
R
10833
30083
40083
Bit 0 = Setback on (1)
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
30084
30086
30088
30090
30092
30094
30096
30098
30100
30102
30104
30106
30108
30110
30112
30114
30116
30117
30118
30119
30120
30121
30122
30123
30124
30125
30126
30127
30128
30128
40084
40086
40088
40090
40092
40094
40096
40098
40100
40102
40104
40106
40108
40110
40112
40114
40116
40117
40119
40119
40120
40121
40122
40123
40124
40125
40126
40127
40128
40129
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Up Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Boiler Valve Down Times (Sec)
Spare
#1
#2
#3
#4
#5
#6
#7
#8
#1
#2
#3
#4
#5
#6
#7
#8
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
2 words per
Spare
Spare
Spare
Spare
Spare
Spare
O/Cdb (Off T>=C, OnT<=OC - O/Cdb)
KPN : Proportional. Constant Numerator (0-255)
KPD : Proportional. Constant Denominator (0-255)
KDN : Differential. Constant Numerator (0-255)
KDD : Differential Constant Denominator (0-255)
Maximum Water Temp
Maximum Water Temp Fault
(0 = OK, 1 = Stpt > Max Temp,
2 = nite Stpt > Max Temp, 3 = Target > Max Temp)
R
R
R
R/W
R/W
R/W
R/W
R/W
30130
30131
30132
30133
30134
30135
30136
30137
40130
40131
40132
40133
40134
40135
40136
40137
Water Sensor
Outdoor Sensor
Spare
(0 = OK, 1 = Open, 2 = Shorted)
(0 = OK, 1 = Open, 2 = Shorted)
O/Cdb ( Off T > = C, On T< = OC - O/Cdb)
KPN : Proportional. Constant Numerator (0-255)
KPD : Proportional. Constant Denominator (0-255)
KDN : Differential. Constant Numerator (0-255)
KDD : Differential. Constant Denominator (0-255)
W
30138
40138
Maximum Water Temperature
A-5
23
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 • FAX (805) 278-5489
Litho in U.S.A.
24
|